- Designs available: Duct version, Wall mounting, Rod-shaped, Room version
- IP 30 with membrane filter
- IP 65 with PTFE sintered filter
- Output signals available:
- 0...1 V / 0...5V / 0...10 V / 4...20 mA / passive
- Operating voltage: 12...30 V DC
- Special version: sealing against vibrations or condensation
General information
Accuracy
Humidity: ± 3% rh 30...80 % rh at 10...40 °C
Temperature ± 0,8 K 10...40 °C
Economical transmitters of the L Series are primarily optimized for ambient room conditions and are very well suited to help control energy costs in HVAC and building automation applications. Thanks to their high-quality manufacturing, these transmitters can also be used in industrial settings under moderate conditions.
Technical data
sensing element | calibrated sensor chip calHT |
output range | 0...100 %rh |
accuracy | |
30...80%rh at 10...40°C | ±3 %rh |
< 30 %rh or > 80 %rh at 10...40°C | ±5 %rh |
influence of temperature < 10°C or > 40°C typ. | ±0.06 %rh/K |
Temperature / active output | |
sensing element | calibrated sensor chip calHT |
output ranges | 0...+50°C |
-20...+80°C | |
-30...+70°C | |
0...+100°C | |
accuracy | |
at 10...40°C | ±0.8 K |
<10°C and >40°C | s. diagramm |
The login area provides you with additional information if you have access authorization.
Do you have questions on this product?
Your contact person:
Badger Meter Swiss AG
Fax. + 41 31 931 08 67
info @badgermeter.ch